  fa wireless ss terminals wt30 1 fa wireless ss terminals wt30 construct a wireless system for on/off data collection that is ideal for monitoring production site equipment ? wireless slave station equipped with i/o.  height of 90 mm and din rail mounting enables installation in control panels.  easily check wireless communications status from indicator display.  i/o slave stations can also be used as slave stations in wd30 systems.  conforms to radio wave standards for japan, china (pending), usa, and europe. ordering information list of models note: an antenna and mounting brackets are not included with the wireless ss terminal. accessories antennas communications cables other applicable standards ? fcc part 15.247 (usa)  en 300 440-2 (europe)  arib std-t66 (japan)  (china) (approval pending) main class 2 power supplies omron switching power supplies  s8vs (15 w, 30 w, 60 w type)  s82k (15 w, 30 w, 50 w, 90 w type) applicable countries wireless standards have been met for the following countries. the product cannot be used in any other countries. austria, belgium, cyprus, czech republic, denmark, estonia, finland, france, germany, greece, hungry, iceland, ireland, italy, japan, latvia, lithuania, luxembourg, malta, netherlands, norway, poland, portugal, slovakia, slovenia, spain, sweden, switzerland, uk, usa wireless unit model type specifications/no. of i/o points wt30-m01-flk serial master rs-232c WT30-SID16 i/o slaves 16 dc inputs (npn/pnp) wt30-smd16 8 dc inputs (npn/pnp) + 8 transistor outputs (npn) wt30-smd16-1 8 dc inputs (npn/pnp) + 8 transistor outputs (pnp) model type wt30-at001 magnet-base antenna (2 antennas per set) wt30-at002 flat diversity antenna (1 antenna) wt30-at003 pencil antenna (2 antennas per set) model length application xw2z-0100u-3 1 m for personal computer xw2z-0200u-3 2 m xw2z-0500u-3 5 m xw2z-0200u-5 2 m cross cable for plc xw2z-0500u-5 5 m model type wt30-ft001 din rail mounting bracket (for th35-7.5) wt30-ft002 din rail mounting bracket (for th35-15) wt30-ft003 surface mounting bracket (screw-mounting) (2 brackets per set) wt30-ft011 flat diversity antenna mounting brackets (with magnets) wt30-ca2m antenna extension cable (1 cable, 2 m) conformity to safety standards always use a class 2 power supply to conform to ul standards. conformity to en standards use a dc power line less than 3 m to conform to en standards. if a power line of 3 m or longer is required, extend the length at the switching power supply?s primary side (i.e., the ac power line).
2 fa wireless ss terminals wt30 specifications ratings note: 1. provide a power supply of at least 15 w, consi dering the inrush current generated at startup. 2. use the wt30-ft003 surface mounting bracket when installing the wt30 in environments subject to vibration. wireless interface specifications note: varies according to the installation environment. package contents ? wt30 fa wireless ss terminal ? terminal labels (i/o slaves only) ? instruction sheet ? adhesive non-slip feet (serial master only) item wt30-m01-flk serial master WT30-SID16/smd16/smd16-1 i/o slaves power supply (wireless communications power supply) rated voltage 24 v dc allowable voltage range 20.4 to 26.4 v dc power consumption 3 w max. (see note 1.) error output/output power supply (for output circuits) rated voltage --- 24 v dc allowable voltage range --- 20.4 to 26.4 v dc insulation resistance 20 m ? min. (at 100 v dc) between the power supply and chassis 20 m ? min. (at 100 v dc) between the power supply and all i/o and i/o power supply and between the power supply and chassis dielectric strength 1,500 v ac for 1 min between power supply and chassis 1,500 v ac for 1 min between the power supply and all i/o and i/o power supply and between the power supply and chassis noise immunity iec61000-4-4. 1 kv (power supply line) vibration resistance (see note 2.) jis c0040 frequency: 10 to 55 hz; amplitude of 0.35 mm or acceleration of 50 m/s 2 , whichever is smaller (din rail mounting: single amplitude of 0.1 mm or acceleration of 15 m/s 2 ) 10 sweeps of 8 min each (i.e., 80 min in total) in x, y, z directions shock resistance conforms to jis c0041: 300 m/s 2 3 times each in x, y, and z directions ambient operating temperature ? 10 to 55c (with no condensation or icing) (with the terminal mounted with the dust-proof label facing up) number of simultaneously on i/o points 10 max.: ? 10 to 55c (with no condensation or icing) 16 max.: ? 10 to 50c (with no condensation or icing) (with the terminal mounted with the dust-proof label facing up) ambient operating humidity 25% to 85% (with no condensation or icing) ambient environment no corrosive gases storage temperature ? 25 to 65c (with no condensation or icing) protective structure ip20 terminal construction power supply and i/o screwless terminal block (phoenix contact ffkds/v1-5.08 or equivalent) serial d-sub, 9-pin (female) inch screws (omron xm2f-0910-132 or equivalent), master station only --- safety standards ul: ul508 (listing) weight 330 g max. item specifications wave type spread spectrum (direct sequence; ds-ss) communication method simplex frequency band 2,401 to 2,480.2 mhz number of channels 67 channels (based on switching) transmitter output power 10 mw/mhz baud rate between wireless stations 100 kbps communications distance (see note.) indoors: 60 m min. (approx. 50 m min. with magnet-base antennas and flat diversity antennas) outdoors: approx. 300 m min. (anticipated distances) (without using relay stations) error detection method crc-ccitt (16 bits) relay functions one stage using i/o slave for the serial master configuration. number of stations per area (see note.) 10 sets max. (recommended) number of i/o slaves connected 64 max.
fa wireless ss terminals wt30 3 nomenclature serial master station i/o slave station unit no. switch set the unit number of the serial master station default: 00 node setting switch (wnode) set the number of connected i/o slave stations. set the node number of the slave stations being used as i/o slave stations. the slave station functions as a relay station when the node number is set to 99. default: 01 channel setting switch (wch) set the communications frequency. default: 02 function setting switch serial master station i/o slave station antenna terminal (ant1) status indicators rs-232c terminal connect the plc, personal computer, etc. power supply terminal supply power to the wt30. unit no. switch set the unit number of the serial master station. node setting switch (wnode) set the number of connected i/o slave stations. channel setting switch (wch) set the communications frequency channel. antenna terminal (ant2) received signal strength indicator special function switch function setting switch make the detailed settings for run/test/set mode. mode selection switch switch between run, test, and set mode. serial communications setting switch set the baud rate. status indicators power supply terminal supply power to the wt30 and output circuits. mode selection switch switch between run, test, and set mode. node setting switch (wnode) set the unit number of the i/o slave station. i/o terminal status indicators (0 to 7 or 8 to 15) the contact status is displayed. channel setting switch (wch) set the communications frequency. antenna terminal (ant2) received signal strength indicator special function switch antenna terminal (ant1) function setting switch make the detailed settings for run/test mode. i/o terminals connect the contact signals. no. applicable mode on functions off functions 1 run mode holds i/o status data when a communications error occurs. clears i/o status data when a communications error occurs. 2 enable scan list disable scan list 3 relays used relays not used 4 test mode signal strength monitor disabled signal strength monitor enabled 5 all channels automatically switched specified channels 6 --- --- 7 set mode scan list recognition nothing done 8 registers specified i/o slave registers all i/o slaves automatically 9 recognizes serial numbers ignores serial numbers 10 not used --- --- no. applicable mode on functions off functions 1 run mode holds i/o status data when a communications error occurs. clears i/o status data when a communications error occurs. 2 input hold normal mode 3 input filter: 100 ms input filter: 10 ms 4 test mode signal strength monitor disabled signal strength monitor enabled 5 all channels automatically switched specified channels 6 installation test function nothing done 7 to 10 not used --- ---
4 fa wireless ss terminals wt30 serial communications setting switch note: for example, if pins number 2, 3, and 4 are all on, the total is 7, which corresponds to a baud rate of 115,200 bps. display note: when using the wd30 as the serial master station, the err indicator will light if normal i/o communications are not possible due to an error in the host network. no. function on off 1 communications setting selection detailed settings (settings for no. 2 to 8 used) default settings (baud rate: 9,600 bps; data length: 7 bits; parity: even; stop bits: 2) settings for no. 2 to 8 are ignored. 2 baud rate (bps) (see note.) total value = 0: 1,200 = 1: 2,400 = 2: 4,800 = 3: 9,600 = 4: 19,200 = 5: 38,400 = 6: 57,600 = 7: 115,200 10 3 20 4 40 5 data length 8 bits 7 bits 6 parity none yes 7 odd even 8 stop bits 1 bit 2 bits indicator color status meaning (primary error) pwr green lit power is being supplied. not lit power is not being supplied. err (slave station) red lit error output is on: wireless device error or wireless communications error. (see note) not lit no wireless device error or wireless communications error. comm (master station) yellow lit serial communications in progress. not lit no serial communications. 0 to 15 (slave station) yellow lit/not lit on/off status for input or output signals rssi red/ yellow/ green lit/ all not lit receiving signal strength indicator monitor: number of indicators lit (receiving signal strength 1 to 9) receiving signal strength less than 0 to 1. ms (module status) green lit communications are normal. flashing test mode or set mode has been activated. red lit a fatal error has occurred that cannot be recovered from. replace the unit flashing a non-fatal error has occurred that can be recovered from by resetting the system. --- not lit power is not being supplied or the system is resetting. ws (wireless status) green lit the station has joined the wireless network. flashing permission to join wireless network received from serial master station (slave station) red lit a fatal error has occurred that cannot be recovered from. flashing error from which recovery is possible --- not lit wireless communications are not in progress.
fa wireless ss terminals wt30 5 wiring serial master station (wt30-m01-flk) i/o characteristics i/o slave station rs-232c connector wt30 power supply terminal supply power to the unit 54321 9876 d-sub, 9-pin, female end at wt30 pin no. signal i/o direction 1 --- --- 2rdoutput 3 sd input 4 --- --- 5 sg --- 6 --- --- 7 --- --- 8 --- --- 9 --- --- vg 01 2 3 com in in 4567 com errp 24 v dc 0 v 8 9 10 11 com 12 13 14 15 com errn power supply inputs inputs inputs inputs error output ( npn ) error output power supply error output (pnp) error output (npn) out 24 v dc 0 v 0 1 2 3 com 4567 com errn power supply outputs outputs vg0 1 2 3 com in 4567 com errp inputs inputs error output/output power supply error output (pnp) WT30-SID16 wt30-smd16 wt30-smd-16-1 item specifications input characteristics input voltage 24 v dc allowable voltage range 20.4 to 26.4 v dc input impedance 4.7 k ? (typical) input current 5 ma (typical) on voltage/ current characteristics 17.4 v dc, 3.0 ma min. off voltage/ current characteristics 5.0 v dc, 1.0 ma max. input filter 10 ms/100 ms (selected using switch.) output/error output characteristics input voltage 24 v dc allowable voltage 20.4 to 26.4 v dc max. switching current 100 ma max. per output (at 20.4 to 26.4 v dc) simultaneous usage of error output npn/pnp is not possible. leakage current 0.1 ma max. residual voltage 1.0 v max. fuse one for every two outputs except for error output circuits, which have one for every npn/ pnp output. (no fuses can be replaced by the user.)
6 fa wireless ss terminals wt30 input circuit diagram error output circuit diagram output circuit diagram (npn) output circuit diagram (pnp) dimensions note: all units are in millimeters unless otherwise indicated. serial master station wt30-m01-flk i/o slave station WT30-SID16 wt30-smd16 wt30-smd16-1 in 0 in 1 in 2 in 15 com (in) secondary internal circuit v g errn errp fuse secondary internal circuit fuse v g out 0 out 1 out 2 out 7 secondary internal circuit fuse fuse fuse v g out 0 out 1 out 2 out 7 fuse out 3 secondary internal circuit fuse four, 5 dia. (15) (15) 60 40 13.3 105 13.3 120 surface mounting bracket wt30-ft003 105 90 7.3 din rail mounting bracket wt30-ft001 or wt30-ft002
fa wireless ss terminals wt30 7 with magnet-base antenna wt30-at001 with flat diversity antenna wt30-at002 with pencil antenna wt30-at003 magnet-base antenna wt30-at001 flat diversity antenna wt30-at002 pencil antenna wt30-at003 din rail mounting bracket wt30-ft001 wt30-ft002 surface mounting bracket wt30-ft003 flat diversity antenna mounting brackets (with magnets) wt30-ft011 (34) (32) (38) 4.6 r38 r40 i/o slave station din rail mounting bracket wt30-ft001 or wt30-ft002 (23) r50 20 i/o slave station din rail mounting bracke t wt30-ft001 or wt30-ft002 150 40 (46) (46) surface mounting bracket wt30-ft003 serial master station 115 2010 39 35.8 dia. 10.5 dia. 57.5 2010 57.5 three, 3 dia. 52 26 10.5 dia . 75
in the interest of product improvement, specifications are subject to change without notice. all dimensions shown are in millimeters. to convert millimeters into inches, multiply by 0. 03937. to convert grams into ounces, multiply by 0.03527. cat. no. n139-e1-01 omron corporation industrial automation company industrial devices and components division h.q. wireless components department shiokoji horikawa, shimogyo-ku, kyoto, 600-8530 japan tel: (81)75-344-7116/fax: (81)75-344-7189 printed in japan 0105


▲Up To Search▲   

 
Price & Availability of WT30-SID16

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X